Epoxy coated vertical tanks 750L-9000L with extractible coils

Datasheet

Tank material steel
Protection EPOXY  coating
Cathodic protection with magnesium rod
Coil steel
Max. working pressure of the tank 10 bar
Max. working temperature 95°C
Max. working pressure of the coil 25 bar
Max. working temperature of the coil 100°C
Insulation Soft P.U. 100mm thick
Outer cover soft PVC

Description

Upon request: Outer cover made by oven painted steel sheet

Three-phase electrical back-up with thermostat DN 1 ½” of 6 or 9 kW

TECHNICAL SPECIFICATIONS BLGLL 750 BLGLL 1000 BLGLL 1500 BLGLL 2000 BLGLL 3000 BLGLL 4000 BLGLL 5000 BLGLL 7000 BLGLL 9000
d Internal diameter mm 800 800 1100 1200 1300 1500 1600 1800 2000
D External diameter mm 1000 1000 1300 1400 1500 1700 1800 2000 2200
H Total height mm 1800 2000 2000 2000 2500 2650 2750 3200 3300
Weight of the cylinder kg 265 405 420 490 645 850 930 1400 1800
Weight of the 3,2 m² coil kg 78 78 78 78 78
Weight of the 5,4 m² coil kg 109 109 109 109 109 109 109
Weight of the 7,8 m² coil kg 154 154
Weight of the outer cover kg 14 16 20 24 34 39 45 58 67
Cylinder thickness mm 4 4 5 5 5 6 6 7 8
Cover thickness mm 4 4 6 6 6 7 7 8 9
Maximum working temperature °C 95 95 95 95 95 95 95 95 95
Maximum working pressure bar 10 10 10 10 10 10 10 10 10
Maximum pressure of the water bar 10 10 10 10 10 10 10 10 10
Maximum working pressure of the coils bar 25 25 25 25 25 25 25 25 25
Insulation ( P.U.) Soft Soft Soft Soft Soft Soft Soft Soft Soft
Insulation’s thickness mm 100 100 100 100 100 100 100 100 100
Maximum working temperature of the coils °C 100 100 100 100 100 100 100 100 100
VEN (ventilation) Inch 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″
Drain Inch 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″
A Hot water outlet HWO mm/Inch 1410/1 1/2″ 1670/1 1/2″ 1680/2″ 1680/2″ 2185/2″ 2245/3″ 2245/3″ 2775/4″ 2775/4″
B Cold water inlet CWI mm/Inch 275/1 1/2″ 295/1 1/2″ 295/2″ 295/2″ 315/2 1/2″ 385/3″ 385/3″ 415/4″ 415/4″
E Recirculation R mm/Inch 1210/1″ 1507/1″ 1495/1 1/2″ 1495/1 1/2″ 1986/1 1/2″ 2050/3″ 2050/3″ 2585/3″ 2585/3″
F Electrical back-up socket ΕΗ2 mm/Inch 1187/1 1/2″ 1198/1 1/2″ 1180/1 1/2″ 1180/1 1/2″ 1490/1 1/2″ 1725/1 1/2″ 1725/1 1/2″ 2280/1 1/2″ 2280/1 1/2″
L Electrical back-up socket ΕΗ1 mm/Inch 500/1 1/2″ 515/1 1/2″ 520/1 1/2″ 520/1 1/2″ 530/1 1/2″ 565/1 1/2″ 565/1 1/2″ 595/1 1/2″ 595/1 1/2″
A Thermometer socket T mm/Inch 1410/1/2″ 1670/1/2″ 1680/1/2″ 1680/1/2″ 2185/1/2″ 2245/1/2″ 2245/1/2″ 2775/1/2″ 2775/1/2″
G Sensor socket ΤR mm/Inch 1210/1/2″ 1507/1/2″ 1495/1/2″ 1495/1/2″ 1985/1/2″ 2050/1/2″ 2050/1/2″ 2585/1/2″ 2585/1/2″
C Sensor socket S mm/Inch 1000/1/2″ 1155/1/2″ 1150/1/2″ 1150/1/2″ 1485/1/2″ 1505/1/2″ 1505/1/2″ 1835/1/2″ 1835/1/2″
I Sensor socket S mm/Inch 510/1/2″ 525/1/2″ 530/1/2″ 530/1/2″ 510/1/2″ 585/1/2″ 585/1/2″ 615/1/2″ 615/1/2″
K Recirculation R mm/Inch 560/1″ 845/1 1/2″ 845/1 1/2″ 1015/1 1/2″ 1035/3″ 2050/3″ 1065/3″ 1065/3″
L Extractible coil C1 mm 500 515 520 520 530/td> 565 565 595 595″
F Extractible coil C2 mm 1187 1198 1180 1180 1490/td> 1725 1725 2280 2280
A Extractible coils’ diameter mm 508 508 508 508 508/td> 508 508 508 508

Additional information

Boiler

από χάλυβα

Επικάλυψη προστασίας

με εποξική ρητίνη

Καθοδική προστασία

με ανόδιο μαγνησίου

Εναλλάκτης

από χαλυβδοσωλήνα

Μέγιστη πίεση λειτουργίας δοχείου

10 bar

Μέγιστη θεμοκρασία λειτουργίας δοχείου

95°C

Μέγιστη πίεση αντοχής εναλλάκτη

25 bar

Μέγιστη θερμοκρασία λειτουργίας εναλλάκτη

100°C

Μόνωση

από μαλακή πολυουρεθάνη (αφρολέξ) 100mm πάχος

Εξωτερική επένδυση

από μαλακό PVC